Abstract
This document provides a preliminary (beta) test plan for grid interconnection systems of advanced inverter-based DERs. It follows the format and methodology/approach established by IEEE Std 1547.1, while incorporating: 1. Upgraded tests for responses to abnormal voltage and frequency, and also including ride-through. 2. A newly developed test for voltage regulation, including dynamic response testing. 3. Modified tests for unintentional islanding, open phase, and harmonics to include testing with the advanced voltage and frequency response functions enabled. Two advanced inverters, one single-phase and one three-phase, were tested under the beta test plan. These tests confirmed the importance of including tests for inverter dynamic response, which varies widely from one inverter to the next.
Original language | American English |
---|---|
Number of pages | 75 |
DOIs | |
State | Published - 2014 |
NREL Publication Number
- NREL/TP-5D00-60931
Keywords
- advanced inverters
- distributed resources
- frequency ride-through
- interconnection testing
- voltage control
- voltage ride-through