Abstract
Simulations have shown that while semi-definite relaxations of AC optimal power flow (AC-OPF) on three-phase radial networks with only wye connections tend to be exact, the presence of delta connections seem to render them inexact. This article shows that such inexactness originates from the non-uniqueness of relaxation solutions and numerical errors amplified by the non-uniqueness. This finding motivates two algorithms to recover the exact solution of AC-OPF in unbalanced distribution networks featuring both wye and delta connections. In simulations using IEEE 13, 37 and 123-bus systems, the proposed algorithms provide exact optimal solutions up to numerical precision.
Original language | American English |
---|---|
Article number | 9380663 |
Pages (from-to) | 3232-3241 |
Number of pages | 10 |
Journal | IEEE Transactions on Smart Grid |
Volume | 12 |
Issue number | 4 |
DOIs | |
State | Published - Jul 2021 |
Bibliographical note
Publisher Copyright:© 2010-2012 IEEE.
NREL Publication Number
- NREL/JA-5D00-79429
Keywords
- delta-connected devices
- distribution networks
- Optimal power flow
- semi-definite relaxation