Field Evaluation of the High Efficiency Dehumidification System (HEDS) at the Timken Museum of Art - Measurement and Verification (M&V) Results from Summer, Winter and Spring Evaluation Periods

Research output: NLRTechnical Report

Abstract

The High Efficiency Dehumidification System (HEDS) technology from Conservant Systems Inc., installed at the Timken Museum of Art in San Diego, California, was evaluated to determine its performance relative to appropriate baseline operation. Data was collected for measurement and verification for several weeks during three evaluation periods: Summer (Aug-Sep 2023), Winter (Dec 2023-Feb 2024) and Spring (May-Jun 2024). The evaluation included operating the heating, ventilation and air conditioning (HVAC) system in both constant air volume (CAV) and variable air volume (VAV) modes, with and without the HEDS energy recovery and HVAC system optimization technology enabled. The electricity consumption of the chiller and the gas-supplied reheat energy were measured to characterize savings achieved by the HEDS operation. Based on these measurements, the HEDS was responsible for chiller electrical load savings during the summer evaluation period of 39% and 42% for the CAV and VAV operating modes, respectively; 97% and 100% chiller electrical load reductions were observed during the winter evaluation for the CAV and VAV operating modes, respectively; and the corresponding reductions during the spring evaluation were 42% and 52% for CAV and VAV operation, respectively. The measured reheat energy reductions, which are typically provided by natural gas, due to the HEDS during summer were 64% and 97% in CAV and VAV operating modes, respectively, while the corresponding values were 99% and 78% during the winter evaluation, and 59% and 56% during the spring evaluation.
Original languageAmerican English
Number of pages44
DOIs
StatePublished - 2025

NLR Publication Number

  • NREL/TP-5500-94847

Keywords

  • dehumidification
  • energy efficiency
  • HVAC
  • natural gas
  • optimized HVAC controls
  • RTU

Fingerprint

Dive into the research topics of 'Field Evaluation of the High Efficiency Dehumidification System (HEDS) at the Timken Museum of Art - Measurement and Verification (M&V) Results from Summer, Winter and Spring Evaluation Periods'. Together they form a unique fingerprint.

Cite this