Abstract
This paper investigates the potential of using brushless excitation (BLE) for not only riding through the fault but also to damp inter-area power oscillation with the help of a synchronous generator (SG) used in Type 5 Wind Power Plant (WPP). In BLE, an auxiliary synchronous generator (ASG) behaving like an exciter is coupled and driven by the rotor of the main SG. The BLE's field current's ASG is fed by two separate loops of the automatic voltage regulator (AVR) and Power System Stabilizer (PSS). The AVR system implements a control loop to regulate the generator terminal voltage, VT. For the PSS, the kinetic energy of the wind turbine is utilized according to the estimated rotational speed of the synchronous generator shaft of the SG. It mitigates the necessity of any curtailment of active power for damping. The effectiveness of the proposed control scheme is verified with a three-phase short circuit fault in a two-area power system.
Original language | American English |
---|---|
Number of pages | 8 |
State | Published - 2023 |
Event | 2023 IEEE Green Technologies Conference - Denver, Colorado Duration: 19 Apr 2023 → 21 Apr 2023 |
Conference
Conference | 2023 IEEE Green Technologies Conference |
---|---|
City | Denver, Colorado |
Period | 19/04/23 → 21/04/23 |
Bibliographical note
See NREL/CP-5D00-87254 for paper as published in proceedingsNREL Publication Number
- NREL/CP-5D00-84738
Keywords
- brushless
- damping control
- dynamic response
- interarea oscillation
- transient stability
- wind power plant