Photovoltaic Inverter Momentary Cessation: Recovery Process is Key

Anderson Hoke, Brian Pierre, Mohamed Elkhatib

Research output: Contribution to conferencePaperpeer-review

9 Scopus Citations

Abstract

Momentary cessation refers to an inverter control mode. When the inverter terminal voltage falls below (or exceeds) a certain level, the inverter ceases to output any current, but attempts to maintain (or quickly regain) phase-locked loop synchronization to allow for quick reinjection of current when the voltage recovers to a certain point. This paper presents a photovoltaic (PV) momentary cessation model developed in PSS/E. Simulations are presented for a high voltage transmission line fault contingency in the Hawaiian island of Oahu power system on a validated PSS/E model, modified to include a custom distributed PV inverter model, and different near-future distributed PV penetration levels. Simulations for the island power system include different penetration levels of PV, and different recovery times (ramp rates and delays) after momentary cessation. The results indicate that during low voltage events, such as faults, momentary cessation can produce severe under frequency events, causing significant load shed and shortly thereafter, in some cases, over frequency events that cause generation to trip offline. The problem is exacerbated with higher penetration levels of PV. If momentary cessation is used (as is typically the case for distribution-connected resources), the recovery process after momentary cessation should be carefully considered to minimize impacts to bulk power system stability.

Original languageAmerican English
Pages1561-1565
Number of pages5
DOIs
StatePublished - Jun 2019
Event46th IEEE Photovoltaic Specialists Conference, PVSC 2019 - Chicago, United States
Duration: 16 Jun 201921 Jun 2019

Conference

Conference46th IEEE Photovoltaic Specialists Conference, PVSC 2019
Country/TerritoryUnited States
CityChicago
Period16/06/1921/06/19

Bibliographical note

Publisher Copyright:
© 2019 IEEE.

NREL Publication Number

  • NREL/CP-5D00-76329

Keywords

  • Frequency control
  • inverter control
  • momentary cessation
  • photovoltaic
  • PV
  • smart inverter

Fingerprint

Dive into the research topics of 'Photovoltaic Inverter Momentary Cessation: Recovery Process is Key'. Together they form a unique fingerprint.

Cite this