Abstract
This study assesses American Society of Heating, Refrigerating and Air-Conditioning Engineers Guideline 36 (G36) with a typical medium office building. Specifically, this study employed a Modelica model of a variable air volume (VAV) system that serves this building, which includes components for representing indoor virus transmission and filtration. It then implemented the G36 control sequences for both water-side and air-side equipment in Python. After that, this study conducted the assessment by co-simulating G36 and the Modelica model using the Building Operations Testing Framework. Unlike existing works, this work has three unique features: (1) It considers the interactions between control sequences for water-side and air-side equipment of the studied VAV system. (2) It assesses the performance of G36 from the perspective of IAQ. (3) It examines the short-term behaviors of the studied building under G36 to understand the control stability. This assessment confirms significant energy savings from G36, largely because of the interaction between supply air temperature and hot water controls. It also reveals a trade-off between the ability to slow the spread of virus and the energy performance via demand controlled ventilation. Lastly, it emphasizes the necessity of tuning local feedback control when implementing G36.
Original language | American English |
---|---|
Number of pages | 15 |
Journal | Building and Environment |
Volume | 240 |
DOIs | |
State | Published - 2023 |
NREL Publication Number
- NREL/JA-5500-86626
Keywords
- advanced building control
- ASHRAE Guideline 36
- control stability
- energy efficiency
- indoor air quality
- Modelica